This Item Is Available To Order £149.95
1.5mm2 2C+E FP PLUS is the 'enhanced' , hard skin, dressable fire resistant cable most commonly needed for fire alarm and emergency lighting circuits as defined by BS5839-1 and BS5266-1.
Cables should meet the performance requirements of BS6387 Category CWZ, EN 50200 PH120, BS 8434-2 120 minutes, BS EN 60332-1-2, BS EN 50266-2-4, BS EN 61034-2 and produce less than 0.5% acidic gases when tested in accordance with BS EN 50267-2-1.
Inner Conductor | Insulation | Overall Tape | Overall Screen | Inner Sheath Material | Outer Sheath | Diameter mm | Min bending radius indoor/outdoor mm | Operating Temp | Weight Kg/1000m |
---|---|---|---|---|---|---|---|---|---|
Plain annealed copper stranded conductor meets the requirements of BS EN 60228 Class 2 | High performance, damage resistant enhanced Insudite™ to meet BS EN 50363-5, Type EI5. Including mica tape for 2c4mm² and all 3 & 4 core. | Polyester backed laminated aluminium or copper tape bonded to outer sheath to provide overall screen. In contact with full sized, tinned annealed copper circuit protective conductor and laid-up with the cores to provide automatic screen earthing | Aluminium/ polyester laminated tape screen | Extruded LSOH | Extruded LSOH suitable for outdoor installation with exposure to normal daylight UV | 9.2 | Radius = 6 x Diameter | Temperature Range -20 to +70˚C | 115 |
Type: FPPLUS2C+E-1.5E